OmniCALL – Assistance Alarm Interface

The OmniCALL OCACIF interface connects an assistance alarm to the Master Station in locations where a standard outstation isn’t practical, occupying a single loop address.

SKU: OCACIF Category: Tag: Manufacturer:

Key benefits

Key benefits

  • Connects an assistance alarm directly to the Master Station without a nearby outstation
  • Self-powered from the loop or radial circuit, no local power source required
  • Occupies a single address at the Master Station
  • Fits a standard 47mm double gang back box, with an optional surface mount back box
  • Green finish

Details

Description

The OmniCALL OCACIF interface connects an assistance alarm directly into the Emergency Voice Communication (EVC) system in locations where installing a full outstation isn’t practical, occupying a single address at the Master Station.

It’s self-powered from the loop or radial circuit, so no local power source is required, and fits a standard double gang back box.

Technical Data

Technical Data

Power supply: 15-36V
Power consumption: 30mA @ 24V
Humidity range: 0-90% non-condensing
Temperature range: -5°C to +40°C
Indicators: Status
Finish: RAL 6024
Dimensions: 150 x 90 mm (W x H)
Back box: Standard double gang (47mm), optional surface mount

Compliance

  • BS 5839-9: Code of practice for design, installation and maintenance of emergency voice communication systems
  • BS 8893: Emergency voice communication (EVC) systems. Components. Specification.